Performance characteristics
● It features excellent technical and economic performance, low temperature rise and strong overload capacity
● It has a long service life and high operational reliability.
● High voltage level design, strong system compatibility, suitable for various scenarios.
● It can withstand high voltage and lightning strikes, and operate stably in various extreme environments.
● It has excellent short-circuit resistance, high mechanical strength and strong resistance to electrodynamic shock
● Low operation and maintenance costs, high operational efficiency, and strong overload capacity.
● Flexible installation, facilitating rapid deployment.
Application scope: Low-voltage distribution networks in urban core areas, distribution systems in small and medium-sized industrial parks, dedicated distribution transformer areas for commercial complexes, distribution projects in new residential communities, distribution networks in the central areas of towns and townships, distribution within the factory areas of general industrial enterprises, and distribution for urban road lighting and public facilities.
10kV Class Main Product Parameters | 35kV Class Main Product Parameters | |
Rated Capacity | 30kVA to 31500kVA | 30kVA to 31500kVA |
Rated Voltage | 4.16~22/0.4kV | 33~38.5/0.4KV |
Reference Standard | IEC,IEEE,UL,GOST | IEC,IEEE,UL,GOST |
Short-circuit Impedance | 4%~6% | 6.5%~8% |
Tap Range | ±5%,±2×2.5% | ±5%,±2×2.5%,±8×1.25% |
Vector Group | Dyn11,Yyn0,Dy1 | Dyn11,Yyn0,Dy1,YNd11 |
Frequency | 50/60Hz | 50/60Hz |